Volvo 150KW 187.5KVA diesel generator set
- Output Power
- 150KW 187.5KVA
- Engine
- Volvo
- Alternator
- Stamford/Marathon/Baifa
- Frequency
- 50HZ/60HZ
150kW 187.5KVA open type diesel power generator set For Sale
Genset Features:
1. Genuine engine
2. Radiator 40°C max,fans are driven by belt, with safety guard
3. Stamford, Marathon, BaiFa
4. Choice of manual/auto and AMF control panels and protection systems
5. Digital auto-start panel
6. Anti Vibration Suspension Absorber
7. Dry type air filter, fuel filter, oil filter
8. 8-hour operation base tank
9. Mould case circuit breaker
10. 24V DC start motor and storage battery
11. Ripple flex exhaust pipe, exhaust siphon, flange, and muffler
12. Comply with ISO and CE standards.
13. All generator sets are gone through rigorous testing before being released to the market place, including 50% load, 75% load, 100% load , 110% load and all protection function (over speed stop, high water temperature, low oil pressure, battery charging fail, emergency stop)
Genset Electrical Performance |
|
Power |
150KW/187.5KVA |
Rated Power Factor |
COSΦ=0.8 |
Rated Output Voltage |
400/230V |
Rated Frequency |
50Hz/60HZ |
Start Control |
Electric |
Voltage Regulation (%): |
≥±0.5 |
Voltage Regulation, Stead State (%): |
≤±0.5 |
Transient voltage regulation rate (%) |
+20~-15 |
Voltage stabilization time: |
3S |
Frequency Regulation, Stead State(%) |
≤±1 |
Frequency Waving(%) |
≤±0.5 |
Transient frequency adjustment rate(%) |
+10~-7 |
Frequency stabilization time: |
≤3 |
Engine Features:
1. Genuine engine
2. Multi-cylinder in-line or veer engine, 4-stroke, direct injection
3. Naturally aspirated, turbocharged, water cooled or turbocharged with air intercooler
4. Machinery or electronic governing
5. Fuel injection pump
6. Electric motor starting system
7. Forged steel crankshaft, cast iron cylinder and replaceable wet type cylinder liner
8. Low discharge, and low fuel consumption
9. Installed conveniently and maintain easily
Diesel Engine Data |
|
Manufacturer: |
Volvo |
Model: |
TAD732GE |
Standby Power: |
150KW |
Rated Speed: |
1500(r/min) |
Cycle: |
6 stroke |
Cylinder Arrangement: |
6 in line |
Displacement: |
3.9L |
Governor Type: |
Electronic |
Start battery voltage: |
24V DC |
Phases |
Three phases, four wires |
Air Intake System: |
Turbo, Water/Air Cooling |
Fuel System: |
PT type fuel pump |
100%( Prime Power) Load: |
213g/kwh |
50%( Prime Power) Load: |
229g/kwh |
Overall Size(mm) |
2600×1050×1670 |
Weight |
1600(kg) |
Alternator Features:
1. Stamford, Marathon, BaiFa etc alternator
2. Brushless, 4 poles, rotation magnet
3. IP21-23(NEMA1) enclose is standard for all industrial alternators
4. H class insulation system
5. Simple installation and maintenance with easy access to terminals, rotating diodes and coupling bolts
6. Wide range of flange adaptors and single bearing disc coupling
7. Radio interference restraining accords with the stipulation of VDE0875-N and ISO8528
8.Mechanical Structure: steel base frame
9. Moisture proof, sand-proof, dustproof, salt-proof and vibration-proof
Alternator Data |
|
Manufacturer: |
BaiFa/STAMFORD/MARATHON |
Excitation Mode: |
Brushless and self- exciting |
Number of phase and Access Act: |
3-phase 4-wire |
Alternator Capacity: |
187.5KVA |
Overload: |
(PRP)110% load can run 1h |
Protection Level: |
IP23 |
Soundproof/Silent Box:
1. Multiple air inlets/outlets ensure power performance of the genset.
2. Large composite impedance muffler effectively reduces the genset noise.
3,Internal high-performance rubber shock absorber and flexible materials can reduce vibration
4. Oil tank mounted on base frame for 8 Hours working
5. Highly Corrosion Resistant construction
6. Excellent Access for Maintenance
7. Security and Safety; Fireproof, waterproof and dust-proof
8. 1m<80DBA / 7m<70DBA
Control Panel:
1. Automatic control panel (AMF), LCD display
2. Four protection systems
3. Emergency stopwith more stringent emission requirements.
Control Data |
|
AC voltage input range |
(50~360)V (phase-N) |
AC input wiring system |
1P-2wire; 2P-3wire; 3P-3wire; 3P-4wire |
Rated frequency |
3-phase 4-wire |
Electricity detection protection |
Voltage, current, power, over & under voltage, loss-phase, anti-phase, over & under frequency, over current and etc. |
Engine detecting |
Coolant temperature, oil pressure,fuel level and speed ect |
Engine protection |
Water high temperature warn or alarm, under oil pressure warn or alarm, over speed warn or alarm and ext. |
Fault alarm |
Yes |
Communication interface RS485, |
Communication interface RS485, standard Modbus-RTU (controller with RS485 only) |
Charging genset excitation (WL or D+) |
Yes |
Charge Failed Warning |
Yes |
Configurable input / output ports |
Yes |